3006349-2022-04-05 6.3 Alarm display and Current list – cause of error Current list 4.5 Current list Alarm 01 2009-02-10 Alarm 02 2009-02-10 Alarm 03 2009-02-10 Alarm 04 2009-02-10 Alarm 05 2009-02-10 01144 10:54:17 02144 11:01:12 03073 18:22:50 12012 18:25:00 13071 19:00:00 Alarms Alarm code 16 alarms Info in EXact Example - list of alarms If an alarm has been generated, an alarm code is shown in the display in the for- mat XXYYZ, where . XX = unit YY = fault code Z = category of alarm. See category table in this section. There can be up to 16 alarms on the "Current list". The first alarm to be added to the queue will be the first alarm to be removed, if there are more than 16 alarms (FIFO principle). shown only in the alarm log list Menu 4.6 36024 is an alarm on EC controller 1 ( 36 024). The alarm description is "The sup- ply voltage to the EC controller is too low" (36 02 4). The category is critical (3602 4 ). Any active alarm is shown under the alarm symbol. If there is more than one alarm, each individual alarm is shown for two seconds on a rotation basis. Category Alarm log list - Menu 4.6 Category (Z) 1 2 Alarm level Effect on operation Info Warning Operation continues Operation continues Icon 3 Alarm Operation continues but with reduced functionality 4 Critical Operation stops 5 Fire Triggered fire alarm procedure mode starts Find troubleshooting directions in the list of alarms via the alarm number. Note: It takes 19 seconds for the list to appear. 62/108
Download PDF fil