3005167-2022-02-02 Operation Menu 8.3.5 Dampers and relays 8.3.5 Dampers and relays LSF > LSA > RGS/AUX OUT > Alarm relay > VDI light > LS ALC > Off Off Off Off Off 0 % The following dampers may be forced open or closed via the menu: ● LSF (closing damper, outdoor air) ● LSA (closing damper, exhaust air) ● LS ALC (closing damper extract air) ● RGS/AUX OUT (flue gas damper) ● The alarm relay may be forced to trigger. ● The light in units fitted with VDI lights may be switched on and off Menu 8.4 - Calibrating MPT NB The pressure transducers (MPT) may only be calibrated when the unit is stopped. The doors should be opened to equalise pressure with the surroundings and to ensure correct calibration. ● Select "Yes" for calibration (automatically changes to "No" again when the MPTs have been calibrated). 8.4 Calibration of MPT MPT1, P1 --- MPT1, P2 --- MPT2, P1 --- MPT2, P2 --- MPT3, P1 --- MPT3, P2 --- MPT4, P1 --- MPT4, P2 --- MPT5, P1 --- MPT5, P2 --- Calibrate > No Last calibrated: Dato 17-05-2017 Tid 10:12:48 Select "Yes" for calibration (automatically changes to "No" again when the MPTs have been calibrated). 60/108