3004525-2017-06-28 Electric heating coil 2.6 Heating coil Electric heating coil: Power step total 1 Active power steps 0 Setpoint 0.0 % TSA60/80 25.0 °C The menu shows: ● number of power steps in heating coil ● Number of active power steps ● output of the modulating step ● internal temperature in electric heating coil control box Operation Menu 2.7 - CH cooling unit 2.7 CH cooling unit Comp. gas press. 0.00bar Suc. gas press. 0.00bar Comp. gas press. 0.00°c Feed temp. 0.00°c Increased airflow Nej Balance Ja Reduction 0% Block start Ja Press. drop rise 0% CH Size --- The menu shows: ● pressure gas pressure ● suction gas pressure ● pressure gas temperature ● supply temperature ● air volume ● balance ● reduction ● blocked start - if the cooling unit is blocked due to the 10-minute interval between starts ● pressure drop rise ● CH size Menu 2.8 - CCW cold water coil 2.8 CCW Fremløb Pumpe 25.0 °C Fra The menu shows: ● Supply temperature for the cold water coil ● Pump - whether circulation pump in cooling circuit is running Menu 2.9 - CU cooling unit 2.9 CU-Køleunit Trykgas temp. 0.0 °C Trykgas tryk 0.0 bar Fordamp. temp. 0.0 °C Reduktion 0.0 % Blok. start Aktiv The menu shows: ● refrigerant temperature ● refrigerant pressure ● evaporation temperature ● reduction - any reduction to cooling output (due to excessive refrigerant temperature) ● blocked start - if the cooling unit is blocked due to the 10-minute interval between starts Menu 2.10 - MXCU external cooling unit 2.10 MXCU Cooling unit Performance Off 0.0% The menu shows: ● If the cooling unit is operating ● Current output of cooling unit 61/112