3004525-2017-06-28 Operation Menu 8.3.2 Heating coil 8.3.2 Heating coil HCE Supply air Min. flow Measured flow Run on Error on unit 0% 0% 0l/s 0l/s No No For electric heating coil HCE: If there are no current faults for the heating coil ("Fault on unit" shown as "No"), forced start may be activated: ● Start the supply air fan and increase its speed until the measured flow is greater than the min. flow ● Then start HCE NB: 8.3.2 Heating coil HCW Error on unit 0% No To avoid the electric heating coil dropping out due to an overheating alarm when the electric heating coil is stopped: ● Do not exit the menu or stop the supply air fan until Run-on is shown as "No". For water heating coil HCW: If there are no current faults for the heating coil ("Fault on unit" shown as "No"), forced start may be activated: ● Enter an output level for HCW to start the motor valve and pump for the water heating coil. Menu 8.3.3 Cooling unit 8.3.3 Cooling unit CCW Error on unit 0% No (The menu screen is different depending on which cooling unit is selected - CH, CCW, MXCU) If there are no current faults for the cooling unit ("Fault on unit" shown as "No"), forced start may be activated: ● Set the output level for the cooling unit Menu 8.3.4 Dampers and relays 8.3.4 Dampers and relays LSF > Off LSA > Off RGS/AUX OUT > Off Alarm relay > Off VDI light > Off BP1 [2.00V] > 2.00V The following dampers may be forced open or closed via the menu: ● LSF (closing damper, outdoor air) ● LSA (closing damper, exhaust air) ● RGS/AUX OUT (flue gas damper) ● Forced tripping of the alarm relay can be provoked ● The light in units with VDI lighting can be switched on and off ● BP1 (bypass damper 1) Menu 8.4 - Calibrating MPT NB The pressure transmitters (MPT) may only be calibrated when the unit is stopped. The doors should be opened to equalise pressure with the surroundings and to ensure correct calibration. ● Select "Yes" for calibration (automatically changes to "No" again when the MPTs have been calibrated). 67/112
Download PDF fil